IINNSSTTAALLLLAATTIIOONN,, OOPPEERRAATTIIOONN && MMAAIINNTTEENNAANNCCEE OOWWNNEERRSS MMAANNUUAALL Model: MICRO MAX 30AC Serial No.:
SET POINT BUTTON TEMPERATURE DISPLAY INSIDE YOUR CHILLER Electrical System: • The controller is powered by 240 volt supply power as well as the
Changing Set points: Setting cooling set point temperature: 1. Press the “SET” key, the symbol “SP” will appear to set desire cooling temperature u
SERVICE BULLETIN HERMETIC COMPRESSOR ELECTRICAL TERMINAL VENTING CAN BE DANGEROUS ****** When the insulating material, which supports a hermetic com
on Tecumseh Products Company drawings and diagrams using the parts as shown on Tecumseh Products Company bills of material. Hermetic compressors can
point if the leads are not properly removed, which can result in the terminal venting and hot oil discharging. No ignition, however, can occur if all
protective device until you have located and corrected the problem. Refer to the Unit Wiring Diagram and Service Manual for the proper procedure and w
MAINTENANCE INFORMATION 1. 2. There are no lubrication points on the chiller. All motors have permanent lubrication in the bearings. The water that
TROUBLE SHOOTING - PART I SYMPTOM DIAGNOSIS REMEDY Compressor won't run Check Power supply Electrical circuit Check Line load
TROUBLE SHOOTING - PART II REFRIGERATION SYSTEM INTERNAL PRESSURE USING REFRIGERANT R-134A * High Pressure Switch : Manual Reset - Cut out at 425
30AC – 230/1 If this unit has special feature(s) installed, see appendix for part number(s). Part Number Description Qty. Refrigeration R30 1/3-H
SchreiberEng ineering12111 EAST PARK ST REETCE RRITOS, CA 90703TITLEMATERIALFINISHSCALE:DRAWING NO.DRAWN BY:DATE:REVDO NOT SCAL E D RAWING16 GA (.0
(562) 926-3855 Schreiber Limited Warranty Schreiber warrants the product described herein against defective mat
TABLE OF CONTENTS Model ………………………………….……………………………….….……………………….. 1 Table of Contents…………………….…………………………….……………………………... 2 Warning – Electr
ELECTRICALJ HAZARDS1) TURNOFFMAIN POWERDISCONNECTSWITCHON THIS MACHINEBEFOREATTEMPTINGTOSERVICETHISEQUIPMENT.2) THIS MACHINEIS PORTABLE.DISCONNECTALL
Specifications: GENERAL Max rated ambient temp. 95 °F Min. Chilled water temp. 44 °F Max Water Temp. 85 °F REFRIGERATION Refrigerant R134A Charge 1 l
STARTUP CHECKLIST • POWER SUPPLY: Verify that the power supplying to the chiller matches the requirements as stated on the nameplate. Connecting chi
8 9 10 111C1C1RModels:Voltage:Options:Schreiber Engineering12111 Park St. Cerritos, CA 90703(562)-926-3855(562)-926-0969 FaxPhase:Type: Air/Water Coo
Schreiber Engineering – Air Cooled Water Chiller Model MICRO MAX series This unit is pre-wired for 230/1. To test unit as follows. ENSURE the s
INSTALLATION 1. Place chiller on level ground. 2. Allow 3-in of clearance in the front and in the back of the unit. This clearance is necessary