***** SPECIAL FEATURE *****
This unit has been modified for
outdoor use
Any reference in this manual
stating “cannot be used for outdoor
installation” does not apply to this unit
The following feature has been added for this
purpose:
Head Pressure Controls
Kit Number: K08.65
Electronic Remote Controls
Kit Number Number: K05.21
With 100 feet of Remote Wire
Kit Number: K09.1D
Vue de la page 0
1 2 3 4 5 6 ... 44 45

Résumé du contenu

Page 1 - ***** SPECIAL FEATURE *****

***** SPECIAL FEATURE ***** This unit has been modified for outdoor use Any reference in this manual stating “cannot be used for outdoor install

Page 2 - SCHREIBER ENGINEERING

SPECIAL CONTROL FEATURES 1) Control LED’s for stage 1 & 2 will indicate "GREEN" when the DIS-CHARGE temperature is above their se

Page 3

SETTING SOLID STATE CONTROL This unit has a solid-state control that controls the temperature on the refrigeration system. After the unit is wired t

Page 6

CHILLED WATER DISTRIBUTION PIPING The chilled water distribution piping is an important factor in the performance of the water chiller. Proper pipi

Page 7

INSTALLATION INSTRUCTIONS Air or Water Cooled Chillers 1. When the chiller is received, check for any shipping damage. If any is found, a freight

Page 8

7. Check the voltage on the chiller to see that it matches your supply. When applying power to the water pump (by turning the manual switch on), mak

Page 9 - +-+-

SPECIAL INSTRUCTIONS WATER PUMP The water pump is controlled by the manual switch for off and on operations. The motor on this pump has a built-in

Page 10 - SPECIAL CONTROL FEATURES

CHILLED WATER CIRCUIT The chilled water is pumped from the chiller's water tank to the discharge outlet of the chiller. Then from the discharg

Page 11

REFRIGERATION SYSTEM: The refrigeration system is a medium temperature system with a range from 35°F to 70°F. This is the most efficient range. If t

Page 12

IINNSSTTAALLLLAATTIIOONN,, OOPPEERRAATTIIOONN && MMAAIINNTTEENNAANNCCEE OOWWNNEERRSS MMAANNUUAALL Model: API Ketema 1001AC Volt

Page 13

FAN MOTOR SPECIFICATIONS Refer to your model number & voltage Model # H.P. Voltage Hz R.P.M. Overload Frame Mounting Rotati

Page 14

14 2. Installation Installation, Operation and Maintenance Instructions. Model NPE/NPE-F DESCRIPT

Page 15

2.3.2. Place unit in position on wedges located at four points (two below approximate cent

Page 16

6.1.1. Single-phase motor: Non-reversible. 6.1.2. Three-phase motor: Interchange an

Page 18

WARNING Overcharging a refrigeration or air conditioning system can be dangerous. **** If a system refrigerant overcharge is sufficient to immerse

Page 19

SERVICE BULLETIN HERMETIC COMPRESSOR ELECTRICAL TERMINAL VENTING CAN BE DANGEROUS **** When the insulating material, which supports a hermetic com

Page 20

Hermetic compressors can be properly serviced without unnecessarily removing the terminal PROTECTIVE COVER by adhering to the following service pro

Page 21 - Model NPE/NPE-F

8. Repeat #5 testing, carefully checking for ground, directly between each compressor terminal (C, S, & R) and ground. 9. If once again a gro

Page 22

Again, we want to stress that it is essential that WHENEVER ELECTRIC POWER is applied to the motor-compressor, the terminal PROTECTIVE COVER must be

Page 24

MAINTENANCE INFORMATION 1. There are no lubrication points on the chiller. All motors have permanent lubrication in the bearings. 2. The wate

Page 25

TROUBLE SHOOTING - PART I SYMPTOM DIAGNOSIS REMEDY Compressor won't run Check Power supply Electrical circuit Check L

Page 26

TROUBLE SHOOTING - PART II REFRIGERATION SYSTEM INTERNAL PRESSURE USING REFRIGERANT R-22 * High Pressure Switch: Manual Reset - Cut out at 42

Page 27

CHILLER PARTS IDENTIFICATION 27

Page 28

PARTS LIST 1001 – 460/3 M.R.I. Unit If this unit has special feature(s) installed, see appendix for part number(s). Part Number Description Qty. Re

Page 29

Plumbing P126-S 3 HP Stainless Steel Water Pump 1 P155 Long Stem Single Float 1 P145-2S Water Pump Seal and “O” Ring Kit 1 P149-WSGA Water S

Page 31 - TROUBLE SHOOTING - PART I

Alarm (Single) E129 Low Ambient Controls 1

Page 32

29 Schreiber Limited Warranty Schreiber warrants the product described herein against defective mate

Page 33

APPENDIX SPECIAL FEATURES

Page 34 - PARTS LIST

TABLE OF CONTENTS Model ……………………………………………………………………………………………… 1 Caution ………………………………………………………………………………………….… 2 Starting Check List ……………………

Page 35

SPECIAL FEATURES Manual Bypass This unit has an adjustable 1” water bypass. It can be adjusted in the field. This feature cuts down the amount of fl

Page 43

WATER CHILLER STARTING CHECKLIST PROPER VOLTAGE Check the voltage on the chiller to see that it matches

Page 44

CONT. WATER CHILLER STARTING CHECKLIST ELECTRIC – POWER A good test to make sure power is off to the unit is to turn on the water pump s

Page 45

L3L2L11C1W1F24VNote: There are two fanmotors on this unit24 VACGroundLow LevPumpCon 1TC INPUTSRETURN DISCHARGE